APM802 - User Manual Regulation Module - MAN31613584001 - EN
APM802 - User Manual Regulation Module - MAN31613584001 - EN
1 INTRODUCTION .................................................................................................3
1.1 REGULATION MODULE P/N 31613584001 .......................................................3
1.2 APPLICATION ......................................................................................................3
1.3 MANUFACTURER.................................................................................................3
2 DECLARATION OF CONFORMITY ..................................................................4
3 WARNING ............................................................................................................5
4 INSTALLATION ...................................................................................................5
4.1 ASSEMBLY ..........................................................................................................5
4.2 EARTHING ...........................................................................................................6
5 TECHNICAL SPECIFICATIONS ........................................................................7
5.1 UNIT ....................................................................................................................7
5.2 ENVIRONMENTAL CONDITIONS ...........................................................................7
5.3 INPUTS AND OUTPUTS CHARACTERISTICS .........................................................8
6 PROTECTIONS ................................................................................................. 10
6.1 SUPPLY CIRCUIT ...............................................................................................10
6.2 ELECTRICAL MEASUREMENT CIRCUITS ............................................................10
7 CONNECTIONS ................................................................................................ 11
7.1 CONNECTION DIAGRAM ....................................................................................11
7.2 CAN COMMUNICATION BUS WIRING ...............................................................12
7.3 CONNECTION SPECIFICATIONS.........................................................................13
7.4 INTERCONNEXION .............................................................................................14
8 MODULE MEASUREMENTS ACCURACY .................................................... 15
9 MAINTENANCE ................................................................................................ 16
10 TROUBLESHOOTING ASSISTANCE ........................................................ 17
10.1 IDENTIFICATION OF DIAGNOSTIC LEDS ............................................................17
10.2 TROUBLESHOOTING .........................................................................................18
1 Introduction
1.1 Regulation Module P/N 31613584001
Regulation module P/N 31613584001:
• Carry out electrical measurements
• Control primary speed and tension regulators according to several regulation
modes, with integrated PIDs including the load regulation in sharing mode,
loading or unloading
• Carry out synchronization and the paralleling
• Carry out functional electric protections
1.2 Application
The regulation module is intended to carry out electrical measures and controls, including
the regulation, for electrical installation equipments, mainly for generating set type
installations.
1.3 Manufacturer
SOREEL
Z.I. du Cormier
18, Rue de la Gâtine
49304 CHOLET Cedex
FRANCE
2 Declaration of conformity
3 Warning
The assembly of this product should only be done by trained technicians.
If the product is used in a way that is not specified in this manual, the protection provided
by the product may be compromised.
. Danger
. Refer to this manual before starting up or using
the equipment
Hazard warning
Risk of electric shock or electric arc
This product may only be installed, used and maintained by trained, qualified personnel,
specifically in accordance with UTEC18510 in France and its equivalent in other countries.
The equipment must be installed in accordance with the installation standards in force in
the country concerned (IEC 60364, NF C 15-100, etc.).
For USA and Canada, installation must be carried out in accordance with NEC/CEC
installation standards.
Before carrying out any work on the product, cut off the product's power supply.
Failure to observe these precautions may result in serious injury.
4 Installation
4.1 Assembly
The regulation module must be installed in electrical equipment such as installation
cabinets, consoles or control units locked using a key or suitable tool.
Select a location that is easy to access.
Mechanical installation may be carried out in the two directions, (vertically or horizontally).
The module is positioned and installed in the equipment using four steel self drilling screws
with a diameter of Ø 4 mm (not supplied) and steel tooth lock washers. The equipment
should be tightened to ensure it is held mechanically.
Place the module in an area where the ambient conditions are suitable for the values it will
accept.
4.2 Earthing
The equipment MUST be earthed.
Earthing can be done via one of the two methods provided :
• Either a short green/yellow wire with a cross-section of 4mm² attached to one of
the two weld studs designed for this purpose, as shown below in A and B.
• Or four steel screws with a diameter of Ø 4 mm with a tooth lock washer, as
shown below at 1, 2, 3 and 4 (not supplied). The earth connection must be made
on a plane connected to the ground.
5 Technical specifications
5.1 Unit
Dimensions : 235mm x 190mm
Protection rate : IP20
Weight : <1.6kg (excluding packaging)
Power supply
Nominal voltage : 24VDC
Voltage range : 9 to 40VDC
Consumption : < 12W
Protected against the inversion of
polarity
SELV circuit
CAN 1 and 2
SELV circuit
Speed regulation
Analog input ±10VDC 100kΩ
Analog output ±10VDC
SELV circuit
Voltage regulation No. 1
Adjustable analog output
±1.25VDC
Isolement : 1500VAC
Relay 3 :
Terminals 251 to 253
240VAC 8A or 30VDC 8A or
48VDC 0,5A
Insulation : Up to 240VAC between
contacts
ETHERNET
6 Protections
6.1 Supply circuit
The supply circuit is protected by a resettable fuse internal to the module.
If this LED is off and the product is however powered, disconnect the power for 10 seconds
to allow the internal fuse module to reset.
A suitable and identified device, to isolate the power supply of the product must be
positioned near the product and without restriction in its operation.
The presence of the power supply is confirmed by a green LED in close proximity of the
terminals 201 and 202.
Green LED
7 Connections
7.1 Connection diagram
Three-phase wiring diagram
N L1 L2 L3 Installation Module de Neutral : Connection with or without
régulation
neutral, neutral recommended on U1 side
L1
U1 "genset" or "power plant" voltage
L2
marker
L3
N
Voltage transformer : With (*) or without
I1
voltage
I2
Transformer
I3
(*) Contact us for the wiring diagram
COM
CAN
Bus Bus
CAN
(*) Required : Black short 4mm² cable between module chassis and primary speed module
ground.
The shielding of the shielded cables must be connected on each end of the cable.
7.4 Interconnexion
Interconnection with other devices :
9 Maintenance
Servicing of the module must be carried out by SOREEL.
SOREEL cannot be held responsible for faults caused by damage, unspecified operating
conditions or failure to observe good practice.
Ensure that the product is being used in line with the specifications.
A damaged or degraded regulation module must be replaced immediately with a new
SOREEL module with the same part number, by personnel qualified to carry out the
operation
important : For each intervention on the product, it is essential to write it down the
software version (On the label stick on the front of the module in the free space at the right
of the RJ45 Ethernet connector) as shown below :
V3.05a 26/05/2010
10 Troubleshooting assistance
10.1 Identification of diagnostic LEDs
Ref LEDs Description
1 Power LED . Green : The module is correctly powered
. Off : The module is not powered
2 CAN bus 1 Communication LED . Quick Flash green : The CAN
3 communication is consistent.
Voyant de communication bus
CAN 2 . Steady green : No CAN communication
. Off : No CAN communication
4 ETHERNET communication link . Yellow : Operational Ethernet link
LEDs . Flash green : Ethernet network activity
5 Activity LED . Flash green : Correct operation
. Steady green or Off : Safety shutdown due
to software fault
6 U2 Voltage detection LED . Steady green : Voltage presence and right
rotating field
7 . Steady red : Voltage presence and wrong
U1 Voltage detection LED
rotating field
1
2
3
7 6 5
4
10.2 Troubleshooting
First of all : Check all the wiring
Noted problem Possible cause Potential solution
CAN No 1 ETHERNET . Incorrect module Address . Check that the address of
communication is . BOOT Mode « ON » the module is correct
impossible . Check that the BOOT mode
is « OFF »
. Restart the module
CAN No 1 and/or No 2 . Incorrect terminating . Check the impedance of the
ETHERNET resistor CAN bus communication,
communication is after having disconnected the
impossible power supply of all the
modules connected to the
CAN bus
. Check that the position of
terminating resistors is
correct
ETHERNET . Incorrect IP address of PC . Check the network
communication is computer configuration of your PC
impossible computer
Measurements are . Incorrect connection of the . Check the connexion of the
inaccurate or do not measurement terminals measurement terminals
match the expected . Check the wiring of VT and
measures. CT
. Incorrect parameters of VT . Check the set values for
and / or CT these parameters
VT = Voltage Transformer CT = Current transformer